Wednesday, 21 June 2017

ACCL - Automatic Source Change Over With Current Limiter

Wednesday, 7 June 2017

Flexible PVC Insulated Cable

PVC- Insulated 1 core unsheathed / Sheathed flexible cord with copper conductor 1.1KV                                         ( As per IS:694 – 1990 )
Nominal Conductor Area (Sq.mm)
UN SHEATHED
SHEATHED
Maximum Conductor Resistance at 20°C (ohm/km)
Current Carrying Capacity (Amp)
Nominal Thickness of Insulation (mm)
Maximum overall Diameter (mm)
Approx. Weight (kg/100m)
Nominal Thickness of Insulation (mm)
Nominal Thickness of Sheath (mm)
Maximum Overall Diameter (mm)
Approx. Weight (kg/100m)
1cX0.5
0.6
2.3
0.9
0.6
0.9
4.5
2.6
39
4
1cX0.75
0.6
2.5
1.2
0.6
0.9
4.7
3
26
7
1cX1
0.6
2.7
1.5
0.6
0.9
4.9
3.4
19.5
11
1cX1.5
0.6
3
2
0.6
0.9
5.4
4.3
13.3
15
1cX2.5
0.7
3.7
3.2
0.7
1
6.2
6
7.98
19
1cX4
0.8
4.4
4.9
0.8
1
7
8.2
4.95
26
1cX6
0.8
5
7
0.8
1
7.4
10.3
3.3
35
1cX10
1
7
11.9
1
1
7.7
13
1.91
46
1cX16
1
9
20.1
1
1
9.8
21.8
1.21
62
1cX25
1.2
10
27.4
1.2
1.1
12
32.1
0.78
80
1cX35
1.2
11.4
36.7
1.2
1.1
13
42.7
0.554
102
1cX50
1.4
13.5
52.5
1.4
1.2
15
59.7
0.386
138
1cX70
1.4
16
72.3
1.4
1.2
17.8
80.6
0.272
214
1cX95
1.6
18
96.1
1.6
1.4
20.7
108.1
0.206
254
1cX120
1.6
20.5
120.3
1.6
1.4
22.2
132.5
0.161
300
          
PVC- Insulated and PVC – Sheathed 2 core flexible cord with copper conductor 1.1KV                                     ( As per IS:694 – 1990 )
Nominal Conductor Area (Sq.mm)
Nominal Thickness of Insulation (mm)
Nominal Thickness of Sheath (mm)
2 CORE CIRCULAR
2 CORE FLAT
Maximum Conductor Resistance at 20°C (ohm/km)
Current Carrying Capacity (Amp)
Maximum overall Diameter (mm)
Approx. Weight (kg/100m)
Maximum overall Diameter (mm)
Approx. Weight (kg/100m)
2cX0.5
0.6
0.9
7.2
5.5
4.9×7.2
4.7
39
4
2cX0.75
0.6
0.9
7.8
6.5
5.2×7.8
5.5
26
7
2cX1
0.6
0.9
8
7.5
5.4×8.0
6.3
19.5
11
2cX1.5
0.6
0.9
8.6
9.2
5.6×8.6
8
13.3
15
2cX2.5
0.7
1
10.5
13.5
6.6×10.5
11.2
7.98
19
2cX4
0.8
1
12
19
7.2×12.0
15.8
4.95
26
          
PVC- Insulated and PVC – Sheathed 3 core flexible cord with copper conductor 1.1KV                                           ( As per IS:694 – 1990 )
Nominal Conductor Area (Sq.mm)
Nominal Thickness of Insulation (mm)
Nominal Thickness of Sheath (mm)
3 CORE CIRCULAR
3 CORE FLAT
Maximum Conductor Resistance at 20°C (ohm/km)
Current Carrying Capacity (Amp)
Maximum overall Diameter (mm)
Approx. Weight (kg/100m)
Maximum overall Diameter (mm)
Approx. Weight (kg/100m)
3cX0.5
0.6
0.9
7.6
6.4
0.9
5.1
39
4
3cX0.75
0.6
0.9
8.2
7.6
0.9
6.1
26
7
3cX1
0.6
0.9
9.2
10.9
0.9
7.1
19.5
11
3cX1.5
0.6
0.9
9.2
10.9
0.9
8.7
13.3
15
3cX2.5
0.7
1
11
16.2
1
13
7.98
19
3cX4
0.8
1
12.5
23.7
1
18.6
4.95
26
1.1 KV SINGLE CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I)
Cross-sectional area        (Sq MM)
UN-ARMOURED CABLE
Overall Diameter (mm)
Normal Current Rating in Amps
Short Circuit Current Rating for 1Sec.duration in K. Amps
Aluminums Conductor
Copper Conductor
Aluminum
Copper
GroundDuctAirGroundDuctAir
1cX4 8 — — — 39 38 35 0.304 0.460
1cX 6 9 39 37 35 49 48 44 0.456 0.690
1cX10 10 51 51 47 65 64 60 0.760 1.150
1cX16 11 66 65 64 85 83 82 1.220 1.84
1cX25 13 86 84 84 110 110 110 1.900 2.88
1cX 35 14 100 100 105 130 125 130 2.660 4.03
1cX50 16 120 115 130 155 150 165 3.800 5.75
1cX70 17 140 135 155 190 175 205 5.320 8.05
1cX 95 19 175 155 190 220 200 245 7.220 10.90
1cX120 21 195 170 220 250 220 280 9.120 13.80
1cX150 23 220 190 250 280 245 320 11.40 17.30
1cX185 25 240 210 290 305 260 370 14.10 21.30
1cX240 28 270 225 335 345 285 425 18.20 27.30
1cX300 30 295 245 380 375 310 475 22.80 34.50
1cX400 35 325 275 435 400 335 550 30.40 46.00
1cX 500 38 345 295 480 425 355 590 38.00 57.50
1cX 630 43 390 320 550 470 375 660 47.90 72.50
1cX800 48 450 380 610 530 425 725 60.80 92.00
1cX1000 52 500 415 680 590 740 870 76.00 115.00
          
1.1 KV SINGLE CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I)
Cross-sectional area        (Sq MM)
ARMOURED CABLE
Overall Diameter (mm)
Normal Current Rating in Amps
Short Circuit Current Rating for 1Sec.duration in K. Amps
Aluminums Conductor
Copper Conductor
Aluminums
Copper
GroundDuctAirGroundDuctAir
1cX4 11 31 30 27 39 38 35 0.304 0.460
1cX 6 12 39 37 35 49 48 44 0.456 0.690
1cX10 13 51 51 47 65 64 60 0.760 1.150
1cX16 14 66 65 64 85 83 82 1.220 1.840
1cX25 15 86 84 84 110 110 110 1.900 2.880
1cX 35 16 100 100 105 130 125 130 2.660 4.030
1cX50 18 120 115 130 155 150 165 3.800 5.750
1cX70 20 140 135 155 190 175 205 5.320 8.050
1cX 95 22 175 155 190 220 200 245 7.220 10.90
1cX120 24 195 170 220 250 220 280 9.120 13.80
1cX150 26 220 190 250 280 245 320 11.400 17.30
1cX185 29 240 210 290 305 260 370 14.100 21.30
1cX240 32 270 225 335 345 285 425 18.200 27.60
1cX300 33 295 245 380 375 310 475 22.800 34.50
1cX400 39 325 275 435 400 335 550 30.400 46.00
1cX 500 42 345 295 480 425 355 590 38.000 57.50
1cX 630 48 390 320 550 470 375 660 47.880 72.50
1cX800 52 450 380 610 530 423 725 60.800 92.00
1cX1000 59 500 414 680 590 471 870 76.000 115.00
          
1.1 KV Two CORE AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES As per IS:1554 (Part-I)
Cross-sectional area        (Sq MM)
UN-ARMOURED CABLE
Overall Diameter (mm)
Normal Current Rating in Amps
Short Circuit Current Rating for 1Sec.duration in K. Amps
Aluminums Conductor
Copper Conductor
Aluminums
Copper
GroundDuctAirGroundDuctAir
2cX4 14 32 27 27 41 35 35 0.304 0.460
 2cX 6 17 40 34 35 50 44 45 0.456 0.690
2cX10 18 55 45 47 70 58 60 0.760 1.150
2cX16 17 70 58 59 90 75 78 1.220 1.840
2cX25 19 90 76 78 115 97 105 1.900 2.880
2cX35 21 110 92 99 140 120 125 2.660 4.030
2cX50 24 135 115 125 165 145 155 3.800 5.750
2cX70 26 160 140 150 205 180 195 5.320 8.050
2cX95 30 190 170 185 240 215 230 7.220 10.90
2cX120 32 210 190 210 275 235 265 9.120 13.80
2cX150 34 240 210 240 310 270 305 11.40 17.300
2cX185 38 275 240 275 350 300 350 14.10 21.280
2cX240 42 320 275 325 405 345 410 18.20 27.600
2cX300 46 355 305 365 450 385 465 22.80 34.500
2cX400 52 385 345 420 490 485 530 30.40 46.000
2cX500 54 425 380 475 540 460 605 38.00 57.500
2cX630 65 465 415 540 640 550 785 47.90 72.550
          
          
          
1.1 KV Two CORE AL/COPPER COND., PVC INSULATEDCABLES As per IS:1554 (Part-I)
Cross-sectional area        (Sq MM)
ARMOURED CABLE
Overall Diameter (mm)
Normal Current Rating in Amps
Short Circuit Current Rating for 1Sec.duration in K. Amps
Aluminums Conductor
Copper Conductor
Aluminums
Copper
GroundDuctAirGroundDuctAir
2cX4 18 32 27 27 41 35 35 0.304 0.460
 2cX 6 19 40 34 35 50 44 45 0.456 0.690
2cX10 20 55 45 47 70 58 60 0.760 1.150
2cX16 20 70 58 59 90 75 78 1.220 1.840
2cX25 22 90 76 78 115 97 105 1.90 2.880
2cX35 23 110 92 99 140 120 125 2.66 4.030
2cX50 26 135 115 125 165 145 155 3.80 5.750
2cX70 29 160 140 150 205 180 195 5.32 8.050
2cX95 33 190 170 185 240 215 230 7.22 10.90
2cX120 35 210 190 210 275 235 265 9.12 13.80
2cX150 37 240 210 240 310 270 305 11.40 17.30
2cX185 41 275 240 275 350 300 350 14.10 21.30
2cX240 47 320 275 325 405 345 410 18.20 27.60
2cX300 50 355 305 365 450 385 465 22.80 34.50
2cX400 58 385 345 420 490 485 530 30.40 46.00
2cX500 64 425 380 475 540 460 605 38.00 57.50
2cX630 72 465 415 540 640 550 785 47.90 72.50